Location: San Jose, CAChiller plant includes 2 chillers, 3 cooling tower cells, and 2 condenser water pumps. Plant load measurements were taken during cooler weather operations. Chiller efficiency impacted by dirty condenser tubes.Chillers were designed for low flow CW of 1.8 gpm/ton-rated and 15 °F temperature range.Base data shows chiller operating with design entering CW temperature of 73.4 °F. With a constant entering CW temperature the data as expected is more organized.Installed (Operating with the CPO) data is scattered reflecting the varying WB and load conditions and the CW set point that ranges between 60 °F to 73.4 °F .
|
||||||