|
Variable Condenser Water
Flow
The specific strategy of Variable Condenser Water Flow
has been overlooked by design engineers and experts in the field because
they felt that the effort to develop this strategy was not worth their time.
If one focuses narrowly on smaller condenser water pump and is not able to
evaluate the broader implications, or the benefits of a pre-packaged
design then it is easy to see how the strategy is often overlooked.
The chiller flow rate is established by the
manufacturer to meet the maximum demand of the chiller and is also based on
the projected performance of a cooling tower. Since the chiller and
cooling tower manufacturers are different, the design criteria becomes
somewhat arbitrary. A typical rule of thumb for chiller cooling is 3
gpm / ton-rated. This is not a fast rule and sometimes where the cooling
tower size is limited the chiller design is re-configured to operate at 2
gpm / ton.
ASHRAE recommends a minimum condenser water flow
velocity of 3.3 ft/sec to maintain turbulent velocity and prevent formation
of deposits in the condenser. This 3.3 ft/sec is well above the low
the 6 to 8 ft/sec encountered in today's chiller designs.
Heat exchange calculations show us that the main factor
in condensing the hot refrigerant gases is a large surface area requirement
for the copper tubes found in most condensers. The water
velocity at the typical design flow rates is a small and nearly negligible
factor in the heat transfer equation. The factor for condensing
efficiency in a chiller is the number and size of tubes and not the water
flow velocity.
A major chiller manufacturer has published papers on
the results of real time chiller operations using various flow velocity
regimes for the condenser water. They were able to operate at very low
flow velocities (and high temperature differentials) without effecting the
stable operation of the chiller. These tests are a matter of public
record.
When employing variable flow energy savings are
realized in several ways:
1.) Reducing the flow of condenser water as a
function of chiller demand not only allows us to obtain direct savings of
pumping energy, it provides a second reason for employing a variable speed
drive on the condenser pumps for balancing purposes and additional savings.
2.) Also, moderately decreasing the flow of
condenser water across the cooling tower increases its performance.
Therefore Variable Condenser Water Flow and Cooling Tower Temperature Relief
can be combined for greater savings then the savings achieved by each
strategy alone.
3.) There are many instances where the condenser
water pumps are much larger than the theoretical chiller plant would seem to
warrant. These conditions include multiple chillers served by a single
condenser circuit with pumps and chillers in a parallel set-up. All of the
pumps have to be designed to meet the worse case pressure and flow
requirements with all systems operating at the same time. Add to that
the fact that these systems tend to have cooling towers located at some
distance from the chillers and the condenser pumps are suddenly nearly as
large as the cooling tower fan motors.
The Chiller Plant Optimizer TM is packaged
controller and instrumentation system that is factory preconfigured with
control solutions to implement this strategy in combination with the other
strategies that are discussed in detail in other articles. Condenser Water
Temperature Reset
All of the low hanging fruit has not been picked!
If your facility uses water cooled chillers it is unlikely that it is using
the optimizing strategy known as Condenser Water Temperature Reset.
For those few sites that employ some form of this strategy, the method of
application in use limits the useful range of control and does not take
advantage of all of the potential savings.
This strategy simply means that the cold water
temperature leaving the cooling tower basin is controlled to a set point
where the set point is allowed to decrease with the changing requirements of
the chiller. It is no secret that refrigeration machines using
common centrifugal or reciprocating compressors are more efficient at lower
condensing temperatures. The conundrum has always been that lowering
the condensing temperature also reduces the chiller's capacity.
The challenge has been to develop a control method that
can adequately match the requirements of the chiller without limiting its
ability to develop full capacity when ever needed. The use of this technique
was relegated to a manual set-back , if used at all until recently.
Several patents have been recently granted for methods that can
reliably achieve provide Condenser Water Temperature Reset on an ongoing
basis.
If you want to whet your appetite on the potential
savings just consider this. Some very efficient chillers have a full
load rating of 0.6 Kw/ton with entering water temperatures of 85° F.
That same chiller can have a part load rating of 0.3 Kw/ton with 65°F
entering water temperature.
There is a trade-off. In order to achieve the
lower temperatures the cooling tower fan will run longer and harder.
Therefore, it is feasible for the cooling tower fan to chew up nearly half
of the energy savings realized by the chiller.
There is a cold water temperature set point that will
significantly reduce the fan energy load and still obtain significant
savings for the entire plant. The three technologies address this
control solution in different but still effective ways. They will also
apply a strategy known here as Cooling Tower Temperature Relief, to limit
the cooling tower fan energy use.
Cooling Tower
Temperature Relief
Cooling Tower Temperature Relief is a difficult
strategy to explain and prove. But we will use an analogy and does not
rely on detail and difficult to follow spread sheets and calculations. Just
know that the developer of the Chiller Plant Optimizer TM has
developed a method of calculating these savings which can be laid out in a
spread sheet format.
Consider a single chiller system of a given size
operating at part load, say 75%. Then compare it to a smaller chiller
system operating at the same load. Say the first example is a
1200 ton chiller (system) operating at 900 tons. And the second
example is a 1000 ton plant operating at 900 tons. Both systems are
then operating with the same outside conditions.
If the smaller chiller system was designed using the
same criteria as the larger system, it will have a smaller cooling tower
with a smaller fan motor. The fan energy use by the smaller system
will be less then the larger system.
Now, since it is impractical to switch to a smaller
cooling tower or smaller fan motor. Cooling Tower Temperature Relief
is simply a control method that insures a similar action by limiting the
maximum speed of the cooling tower fan motor.
The standard control method for cooling towers uses a
temperature sensor for the cold water (basin temperature) and controls the
fan to achieve this temperature. A control method that provides for
Cooling Tower Temperature Relief requires additional information then cold
water temperature. The control may reset the cold water temperature
set point, or use some other control strategy, that results in a different
and possibly slightly higher cold water temperature then the primary (or
full load design) cold water temperature.
As an independent strategy the savings are limited for
Cooling Tower Temperature Relief, and must be applied very judiciously.
But as a strategy combined with Condenser Water Temperature Reset it is a
very effective tool for energy optimization.
Multiple Chiller
Optimizing Strategies
Multiply chiller management can not be applied across
the board as a simple strategy. The different types of chillers as well as
their size drives the decision matrix to determine the operational sequence
and combinations.
Therefore we look at the “art” of multiple
chiller management strategies. More then any other strategy, this one
can backfire and it has lead to unnecessary and costly equipment
installations that in the end did not lead to energy savings, and is one
reason that this strategy that must be carefully considered and then
reconsidered, when or if new chiller purchases are involved.
The available savings from a complicated management
strategy is limited. Also, if the strategies of Variable
Condenser Water Flow, Condenser Water Temperature Reset, and Cooling Tower
Relief have already been applied then additional savings from other
strategies are limited.
With the Chiller Plant Optimizer TM an
optional method of control can be added for each chiller so that a strategy
tailored for the chiller plant can be employed independently of the existing
chiller plant of building automation control.
Chilled Water
Reset as an Optimizing Strategy
The strategy of Chilled Water Temperature Reset,
can not be applied across the board and is considered an optional strategy
that can be applied for simple environmental situations where personnel
comfort is the only consideration.
Chilled water flow of 1000 gpm that leaves the
condenser barrel at 45° F. and returns at 50° F. is 416 tons of
refrigeration. That same flow rate of 1000 gpm leaving the condenser
barrel at 50° F. and returning at 55° F. is still 416 tons of refrigeration.
The difference is that under the second condition the chiller produced the
same refrigeration with much less work or with less energy.
Reason tells us that we can save energy by raising the
leaving chilled water temperature set point. But we are also aware
that the various systems through-out the facility were designed for a
selected cold water temperature which determined equipment size such as fans
and coils. Therefore, any client operation requiring chilled water,
operating at its full design load will be adversely affected by a high
chilled water temperature. Also any operation with special humidity
control requirements will be adversely affected by a higher then design
chilled water temperature.
Another effect of raising the chilled water temperature
will mean that distribution pumps and fan coil units may be required to
operate longer and harder when the chilled water temperature is above the
design temperature.
Due to the above difficulties above the application of
this strategy it is arguable that application should be limited.
Perhaps employed where the primary and important loads are simple and
can handle some flexibility, and where the effect of outside
conditions and operational loads are clearly understand and are
cyclical such as an office building that is lightly loaded at night and on
weekends.
Chilled water reset when used for the systems described
in the previous paragraph can be easy to implement and provide some nice
savings. Some control methods use a load based system to simply
implement chilled water reset. The good thing about such a system is
that it is easy to easy to configure, and or reconfigure by the operator to
achieve an optimal compromise between comfort and energy savings. A
some what more sophisticated control might use a method that not only
considers the chillers operation but also the effect of outside conditions
on the chiller and thus a more reliable way to adjust to the buildings
overall requirements. This is still a system that can still be easily
configured or reconfigured by the operator.
The savings are not as dramatic as the other
strategies, but still worth considering if conditions allow. It
can also be combined with the strategies of Cooling Tower Temperature
Relief, Condenser Water Temperature Reset, and Variable Condenser Water Flow
as an optional addition to the Chiller Plant Optimizer TM
providing a boost to the overall savings and payback, and supporting
our goal for a 25% reduction in overall energy use.
Performance
Monitoring for Chiller Plants
The HVAC industry has been loath to provide and install
meaningful tools to monitor the performance of chiller plants in a
meaningful manner. When it does the results are so limited that the their
usefulness is problematic. We propose a systematic and methodical method
that can be used to compare results with other chiller plants providing
similar service and even with some not so similar.
- Measure the output of the chiller plant, don’t make
assumptions from chiller data. That means one measures the actual
BTU’s of cooling that is produced, preferably as near the chillers as
possible.
- Measure real power consumed, don’t use amperage and
assume that definitive results can be calculated. Real power means Kw
including power factor, not KVA.
- Only include the chiller, condenser pumps, and
cooling towers. In this manner the long term results will be more
meaningful from year to year and sensible comparisons can be made for
plant to plant.
- Provide an executive report on a periodic basis that
is easy to read and can be analyzed by management in 60 seconds or less.
- This means recording data on a continuous basis so
that true averages for various operating periods, night vs day and
weekend vs week day can be reported, if necessary.
- Produce a single meaningful number. That is say it
in Kw/Ton.
(Step four may be the most challenging, because people
will have to be trained to accept the Kw/Ton as a measuring tool.
Also the temptation to include the recirculation and distribution pumps may
be overwhelming. Think of the distribution side as the customer’s
responsibility not part of the producer’s responsibility. Many chiller
plants look similar, until one includes the distribution of the chilled
water. )
|